Features:
Relay output: changeover contact (N.O. and N.C.)
Switching capacity with a resistive load: 16A/230Vac max.
Switching capacity with an inductive load: 8A/230Vac max.
Suppressed relay contacts.
Manual control on the module
LED indicators for:
Relay output
Operation modes (slow, fast, very fast or 2 x blinking and continuously ON)
Power voltage
Data reception and forwarding through VELBUS
10 different operation modes (adjustable through ‘mode’l rotary switch):
Moment control
On/off control
Start/stop timer
Staircase lighting timer
Non-restartable timer
Switch-off delay
Switch-on delay
Start timer by releasing push button
Timer with blinking effect
2-way timer (short press will start timer 1/ long press will start timer2)
16 possible time settings (adjustable through ‘time1’ rotary switch): moment - 5s - 10s - 15s - 30s - 1min - 2 min
- 5min - 10min - 15min - 30min – 1h – 2h – 5h – 1day – on/off
9 possible time settings for timer 2 (adjustable through ‘time2’ rotary switch): 5min - 10min - 15min - 30min – 1h
– 2h – 5h – 1day – on/off
Controllable by connecting several push buttons in parallel.
Push button input debounce: 65ms.
Control through VELBUS.
Programmable without PC.
Easy learning process by controlling the push buttons in the learning mode.
8 different control possibilities:
Using push buttons turning on the relay.
Using push buttons turning off the relay.
Using push buttons turning the relay on or off.
Using push buttons activating the set mode on the module.
Using push buttons starting or stopping the timer.
Using push buttons starting or stopping the 2nd timer.
Using push buttons starting or restarting the timer.
Using push buttons starting or restarting the 2nd timer.
Memory for 7 different push buttons per command
Learned push buttons are saved in case of a power failure.
Report to control modules for LED status modification.
247 possible addresses (adjustable through ‘ADDR” rotary switch)
Required power voltage: 12 to 18VDC
Consumption in standby: 35mA at 18V (15mA at 16V)
Consumption activated relay: 85mA at 18V (60mA at 16VDC)
Max. consumption (activated relay and push button input): 100mA at 18V (75mA at 16VDC)
Standard DIN-rail housing (2 modules)
Dimensions (L x W x H): 90 x 36 x 58mm.
Weight: 100g.